NSN | Description | Assign | Criticality | Status | Codification Country |
---|---|---|---|---|---|
5925000882498 | CIRCUIT BREAKER | 12/29/1967 | X | Pending Cancellation |
Issued | Closing | Solicitation | Clin | Cage | ECV | Status |
---|
Part Number | Company | Cage | P/N added | P/N deleted | RNVC | RNCC | RNAAC | RNFC | SADC | DAC | Item Status |
---|---|---|---|---|---|---|---|---|---|---|---|
APGH-111-1REC2-62-203-90 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
922572-1 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
JA3S-A2A3A3-ES-01-D-05-20-2 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
JA3-A2A3A3-20-2 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
Company | Cage | Award Date | Qty | Unit Price | Total Price | Contract | Delivery |
---|
MOE | SOS | AAC | Unit Pack | UOM | Unit Price | SLC | Date ELA | FCS | MCC |
---|---|---|---|---|---|---|---|---|---|
Army | SMS | Y | 1 | EA | 46.47 | 0 | 10/01/2022 | Q2200 | |
DLA | SMS | Y | 1 | EA | 46.47 | 0 | 10/01/2022 |
Name | Value |
---|---|
BODY LENGTH | 2.000 INCHES NOMINAL |
THREAD SERIES DESIGNATOR | UNC |
THREAD PITCH DIAMETERS | +0.1177 TO 0.1214 INCHES |
MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CASE MATERIAL | PLASTIC |
MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS |
POLE QUANTITY | 3 |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 30.0 DC |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.000 INCHES MAXIMUM |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HERMETICALLY SEALED AND SHOCK RESISTANT AND VIBRATION RESISTANT |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
ACTUATOR FUNCTION | TRIP-RESET |
NOMINAL THREAD SIZE | 0.138 INCHES |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.660 INCHES NOMINAL |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
RESET METHOD | MANUAL |
BOSS HEIGHT | 0.130 INCHES NOMINAL |
SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND 5.0 DC |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE TWO |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3500.0 AC ALL LOCATIONS |
THREAD QUANTITY PER INCH | 32 |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
SWITCH TERMINAL TYPE | QUICK DISCONNECT, MALE |
SPECIAL HANDLING FEATURE | MAGNETIC |
FRAGILITY FACTOR | MODERATELY RUGGED |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.530 INCHES NOMINAL |
SPECIAL FEATURES | ACTUATOR WHITE WITHOUT MARKINGS |
FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
BODY WIDTH | 2.265 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT, MALE |
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
FIIG | INC | Description | Detail |
---|---|---|---|
00136 | 00136 | CIRCUIT BREAKER |
Country | MOE | AMC | AMSC | NIMSC | Eff Date | IMC | IMCA | DSOR | Collaborator | Receiver | AAC | FMOE |
---|---|---|---|---|---|---|---|---|---|---|---|---|
YD01 | 08/01/2016 |
Integrity | Originating | HMC | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
TX | 72D | Z | 9 | A | H | Z | W | 063160 | Z | 35205 | SWITCH BOXES/ELEC ENCLOSURES |
Source | PICA / SICA | Packaging Category | Storage | Preservation | Clean/Dry | INT Qty | Unit Weight | Unit Size | Unit Pack Cube | Item Weight | Item Dims |
---|---|---|---|---|---|---|---|---|---|---|---|
P | P | 69F0 | B | 41 | 1 | AAA | 0.1 lbs | 0.001 cu ft |
Preservation Material | Wrapping Material | Cushioning / Dunnage | Cushioning Thickness | Unit Container | Intermediate Container | UCL | Special Marking | Level A Packing | Level B Packing | Minimal Packing | Optional Procedure |
---|---|---|---|---|---|---|---|---|---|---|---|
00 | FA | BG | C | D1 | DO | 00 | Q | Q | O |
Status Code | Originator | Date | Status |
---|---|---|---|
Authorized for Procurement | TX | 08/24/1968 | Pending Cancellation |