NSN | Description | Assign | Criticality | Status | Codification Country |
---|---|---|---|---|---|
5925002997809 | CIRCUIT BREAKER | 01/01/1963 | X | Active |
Issued | Closing | Solicitation | Clin | Cage | ECV | Status |
---|
Part Number | Company | Cage | P/N added | P/N deleted | RNVC | RNCC | RNAAC | RNFC | SADC | DAC | Item Status |
---|---|---|---|---|---|---|---|---|---|---|---|
50-309M6-30 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
SB1612-5 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
50143-5 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
50-309MG3-30 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
Company | Cage | Award Date | Qty | Unit Price | Total Price | Contract | Delivery |
---|
MOE | SOS | AAC | Unit Pack | UOM | Unit Price | SLC | Date ELA | FCS | MCC |
---|
Name | Value |
---|---|
FRAGILITY FACTOR | MODERATELY RUGGED |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC SINGLE LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
BODY LENGTH | 3.709 INCHES MINIMUM AND 3.729 INCHES MAXIMUM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.611 INCHES NOMINAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 5.500 MINIMUM AT 200 PCT AND 19.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
NOMINAL THREAD SIZE | 0.138 INCHES |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
THREAD QUANTITY PER INCH | 32 |
BOSS HEIGHT | 0.146 INCHES MINIMUM AND 0.166 INCHES MAXIMUM |
RESET METHOD | MANUAL |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
ACTUATOR FUNCTION | TRIP-RESET |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CASE MATERIAL | PLASTIC |
MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.052 INCHES MINIMUM AND 3.072 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 AC SINGLE LOCATION |
POLE QUANTITY | 1 |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
BODY WIDTH | 0.980 INCHES MINIMUM AND 1.000 INCHES MAXIMUM |
BODY STYLE | SINGLE POLE TYPE |
FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
THREAD SERIES DESIGNATOR | UNC |
TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
FIIG | INC | Description | Detail |
---|---|---|---|
00136 | 00136 | CIRCUIT BREAKER |
Country | MOE | AMC | AMSC | NIMSC | Eff Date | IMC | IMCA | DSOR | Collaborator | Receiver | AAC | FMOE |
---|---|---|---|---|---|---|---|---|---|---|---|---|
ZP01 | 04/01/1991 | |||||||||||
ZU01 | 04/01/1991 |
Integrity | Originating | HMC | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
XX | 658 | Z | 9 | A | H | Z | M | 061360 | X | 34430 | COILS/YOKES FOCUS/DEFLECTION TV |
Source | PICA / SICA | Packaging Category | Storage | Preservation | Clean/Dry | INT Qty | Unit Weight | Unit Size | Unit Pack Cube | Item Weight | Item Dims |
---|---|---|---|---|---|---|---|---|---|---|---|
Preservation Material | Wrapping Material | Cushioning / Dunnage | Cushioning Thickness | Unit Container | Intermediate Container | UCL | Special Marking | Level A Packing | Level B Packing | Minimal Packing | Optional Procedure |
---|---|---|---|---|---|---|---|---|---|---|---|
Status Code | Originator | Date | Status |
---|---|---|---|
Authorized for Procurement | TX | 12/15/1974 | Active |