NSN | Description | Assign | Criticality | Status | Codification Country |
---|---|---|---|---|---|
5925004814090 | CIRCUIT BREAKER | 10/07/1972 | X | Active |
Issued | Closing | Solicitation | Clin | Cage | ECV | Status |
---|
Part Number | Company | Cage | P/N added | P/N deleted | RNVC | RNCC | RNAAC | RNFC | SADC | DAC | Item Status |
---|---|---|---|---|---|---|---|---|---|---|---|
MIL-C-55629/4 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
AM33HKMG6-10-250VAC400C15 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
260-4065-080 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
MIL-PRF-55629/4 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
M55629/4-082 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
APL11R554-080 | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### | ######### |
Company | Cage | Award Date | Qty | Unit Price | Total Price | Contract | Delivery |
---|
MOE | SOS | AAC | Unit Pack | UOM | Unit Price | SLC | Date ELA | FCS | MCC |
---|
Name | Value |
---|---|
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
THREAD PITCH DIAMETERS | +0.1177 TO 0.1214 INCHES |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
ACTUATOR FUNCTION | TRIP-RESET |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
THREAD QUANTITY PER INCH | 32 |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.100 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.719 INCHES MINIMUM AND 0.781 INCHES MAXIMUM |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.800 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.719 INCHES MINIMUM AND 0.781 INCHES MAXIMUM |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
RESET METHOD | MANUAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.046 INCHES MINIMUM AND 2.078 INCHES MAXIMUM |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
POLE QUANTITY | 2 |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT |
SPECIAL HANDLING FEATURE | MAGNETIC |
FRAGILITY FACTOR | MODERATELY RUGGED |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.660 INCHES MINIMUM AND 1.960 INCHES MAXIMUM |
BOSS HEIGHT | 0.109 INCHES MINIMUM AND 0.171 INCHES MAXIMUM |
SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND 2.0 DC |
NOMINAL THREAD SIZE | 0.138 INCHES |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 50.0 DC |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC ALL LOCATIONS |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
SPECIFICATION/STANDARD DATA | 81349-MIL-C-55629/4 GOVERNMENT SPECIFICATION |
BODY LENGTH | 2.510 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
THREAD SERIES DESIGNATOR | UNC |
BODY WIDTH | 1.437 INCHES MINIMUM AND 1.563 INCHES MAXIMUM |
TEST DATA DOCUMENT | 81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
FIIG | INC | Description | Detail |
---|---|---|---|
00136 | 00136 | CIRCUIT BREAKER |
Country | MOE | AMC | AMSC | NIMSC | Eff Date | IMC | IMCA | DSOR | Collaborator | Receiver | AAC | FMOE |
---|---|---|---|---|---|---|---|---|---|---|---|---|
ZW01 | 11/01/1998 | |||||||||||
ZG01 | 04/01/1991 |
Integrity | Originating | HMC | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
TX | 658 | Z | 9 | A | H | Z | M | 061360 | X | 34430 | COILS/YOKES FOCUS/DEFLECTION TV |
Source | PICA / SICA | Packaging Category | Storage | Preservation | Clean/Dry | INT Qty | Unit Weight | Unit Size | Unit Pack Cube | Item Weight | Item Dims |
---|---|---|---|---|---|---|---|---|---|---|---|
Preservation Material | Wrapping Material | Cushioning / Dunnage | Cushioning Thickness | Unit Container | Intermediate Container | UCL | Special Marking | Level A Packing | Level B Packing | Minimal Packing | Optional Procedure |
---|---|---|---|---|---|---|---|---|---|---|---|
Status Code | Originator | Date | Status |
---|---|---|---|
Authorized for Procurement | TX | 12/01/1974 | Active |