5925006863327

CIRCUIT BREAKER

Part No.: MP160,

NSN Summary
NSN Description Assign Criticality Status Codification Country
5925006863327 CIRCUIT BREAKER 01/01/1963 X Active

Open Solicitations

Issued Closing Solicitation Clin Cage ECV Status

Request A Demo

Request a Demo to see all details.

Request Demo

Manufacturers

Part Number Company Cage P/N added P/N deleted RNVC RNCC RNAAC RNFC SADC DAC Item Status
MP160 ######### ######### ######### ######### ######### ######### ######### ######### ######### ######### #########

Request A Demo

Request a Demo to see all details.

Procurement History

Company Cage Award Date Qty Unit Price Total Price Contract Delivery

Request A Demo

Request a Demo to see all details.

Request Demo

Management Data

MOE SOS AAC Unit Pack UOM Unit Price SLC Date ELA FCS MCC

Technical Info

Name Value
OVERALL LENGTH 2.578 INCHES NOMINAL
OVERALL HEIGHT 2.188 INCHES NOMINAL
MOUNTING FACILITY TYPE AND QUANTITY 2 THREADED STUD
TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION
ARC QUENCHING METHOD AIR
MANUAL ACTUATOR TYPE AND QUANTITY 1 PUSH-PULL
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 15.000 MINIMUM AT 200 PCT AND 55.000 MAXIMUM AT 200 PCT AND 2.000 MINIMUM AT 400 PCT AND 7.000 MAXIMUM AT 400 PCT SINGLE LOCATION
CASE MATERIAL PLASTIC
TRIP RELEASE METHOD MAGNETIC SINGLE LOCATION
POLE QUANTITY 1
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 120.0 AC AND 30.0 DC SINGLE LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 60.0 AMPERES AC AND 60.0 AMPERES DC SINGLE LOCATION
CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
RESET METHOD MANUAL
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 115.0 SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 1.813 INCHES NOMINAL
ACTUATOR FUNCTION RESET
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 3500.0 AC AND 6000.0 DC SINGLE LOCATION
OVERALL WIDTH 0.750 INCHES NOMINAL
TERMINAL TYPE AND QUANTITY 2 SCREW

A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.


FIIG Inc Info

FIIG INC Description Detail
00136 00136 CIRCUIT BREAKER

MOE Data

Country MOE AMC AMSC NIMSC Eff Date IMC IMCA DSOR Collaborator Receiver AAC FMOE
ZC01 04/01/1991

Freight Data

Integrity Originating HMC WCC TCC SHC ADC ACC ASH LTL NMFC NMFC Sub Item UFC Freight Description Rail Variance
XX 658 Z 9 A H Z M 061360 X 34430 COILS/YOKES FOCUS/DEFLECTION TV

Packaging Data

Source PICA / SICA Packaging Category Storage Preservation Clean/Dry INT Qty Unit Weight Unit Size Unit Pack Cube Item Weight Item Dims
Preservation Material Wrapping Material Cushioning / Dunnage Cushioning Thickness Unit Container Intermediate Container UCL Special Marking Level A Packing Level B Packing Minimal Packing Optional Procedure

Item Standardization

Status Code Originator Date Status
Authorized for Procurement TX 12/03/1969 Active